Schneider Electric NQ820B1C Column Width Panelboard

Technical Specification

Features:
  • Make: Schneider Electric
  • Model code: NQ820B1C
  • Type: Main breaker
  • Application: Industrial
  • Number of Phases: 1
Read more
Additional info:

240 Vac maximum (NQ) or 480Y/277 Vac maximum (NF) 100 - 225 Amp main circuit breaker or main lugs 65kA maximum fully rated branch SCCR (@ 480Y/277 Vac for NF, or @ 240 Vac for NQ) 60 Amp maximum branch circuit breaker Accepts plug-on (NQ) or bolt-on branch circuit breakers (NQ or NF) Solid neutral located on same end as mains Galvanized steel enclosure with removable endwalls Finish: gray-baked enamel electrodeposited over cleaned, phosphatized steel All lugs are suitable for 75° C copper or aluminum wire

Read more
Make Schneider Electric
Manufacturer Schneider Electric
Category Transmission and Distribution>Panelboards
Model code NQ820B1C
Type Main breaker
Application Industrial
Number of Phases 1
Max. Voltage 240 V AC
No. of spaces 20
Max. Current 100 A
Wiring configuration 3-wire
Busbar Material Copper
Width 8.625 in
Depth 5 in
Height 40 in
Standards CSA, UL
Additional info
  • 240 Vac maximum (NQ) or 480Y/277 Vac maximum (NF)
  • 100 - 225 Amp main circuit breaker or main lugs
  • 65kA maximum fully rated branch SCCR (@ 480Y/277 Vac for NF, or @ 240 Vac for NQ)
  • 60 Amp maximum branch circuit breaker
  • Accepts plug-on (NQ) or bolt-on branch circuit breakers (NQ or NF)
  • Solid neutral located on same end as mains
  • Galvanized steel enclosure with removable endwalls
  • Finish: gray-baked enamel electrodeposited over cleaned, phosphatized steel
  • All lugs are suitable for 75° C copper or aluminum wire