Features:
  • Make: Schneider Electric
  • Model code: NF418L1C
  • Type: Main lugs
  • Application: Industrial, Commercial
  • Number of Phases: 3-phase
Read more
Additional info:

UL Listed to 800 A at 480Y/277Vac (cUL rated to 600Y/347 Vac) Fully rated to 65 kA SCCR @ 480Y/277 Volts (Series rated to 200 kA) 15 – 125 Amp HACR rated bolt-on branch circuit breakers with VISI-TRIP® indication (HID rated up to 50A; 1φ SWD rated to 20A) NEMA Type 1, 2, 3R, 4, 4X, 5, and 12 enclosures Interiors are field convertible to top or bottom feed Aluminum or Copper bus Suitable for use as service equipment Field installable main breaker accessories: undervoltage release, alarm switch, and auxiliary contacts Modular construction to accept field installable accessories and conversion kits: sub-feed lugs, thru-feed lugs, and sub-feed circuit breakers main circuit breakers and kits up to 600A 200% rated neutrals for non-linear loads Rail and dead front extension kits provide space for future addition of ready-to-install kits (extensions of 6", 12", 18”, and 24” available) Copper and aluminum, mechanical and crimp lugs

Read more
Make Schneider Electric
Manufacturer Schneider Electric
Category Transmission and Distribution>Panelboards
Model code NF418L1C
Type Main lugs
Application Industrial, Commercial
Number of Phases 3-phase
No. of spaces 18
Max. Current 125 A
Wiring configuration 4-wire
Busbar Material Copper
Width 10.44 in
Height 21 in
Standards CSA C22.2, UL 67
Additional info
  • UL Listed to 800 A at 480Y/277Vac (cUL rated to 600Y/347 Vac)
  • Fully rated to 65 kA SCCR @ 480Y/277 Volts (Series rated to 200 kA)
  • 15 – 125 Amp HACR rated bolt-on branch circuit breakers with VISI-TRIP® indication (HID rated up to 50A; 1φ SWD rated to 20A)
  • NEMA Type 1, 2, 3R, 4, 4X, 5, and 12 enclosures
  • Interiors are field convertible to top or bottom feed
  • Aluminum or Copper bus
  • Suitable for use as service equipment
  • Field installable main breaker accessories: undervoltage release, alarm switch, and auxiliary contacts
  • Modular construction to accept field installable accessories and conversion kits:
    • sub-feed lugs, thru-feed lugs, and sub-feed circuit breakers
    • main circuit breakers and kits up to 600A
    • 200% rated neutrals for non-linear loads
    • Rail and dead front extension kits provide space for future addition of ready-to-install kits (extensions of 6", 12", 18”, and 24” available)
    • Copper and aluminum, mechanical and crimp lugs