Schneider Electric FBX3NC0312A21WOC2O Gas-Insulated Ring Main Unit up to 24 kV

Technical Specification

Features:
  • Make: Schneider Electric
  • Model code: FBX3NC0312A21WOC2O
  • Series: FBX
  • Type: Gas insulated switchboard
  • Max. Voltage: 12 kV
Read more
Additional info:

SF6-insulated switchgear for secondary distribution network SF6 switch-disconnector Protection through fuse combination or vacuum circuit-breaker Two versions : FBX-C (Compact), FBX-E (Extensible) Compliant with IEC 62271-200 Rated Voltage: 12 / 17.5 / 24 kV Bus-bar Rated Current: 630 A Feeder Rated Current: 630 A Rated Short Time Withstand Current : up to 21 kA 3s (up to 25 kA 1s for 12 kV) Internal Arc Containment : up to 25 kA 1s Dimensions W x H x D in mm: 2 switch-disconnectors + circuit-breaker or fuse protection functions: 1000 x 1380 x 750 Option : can be remotely controlled and monitored through a RCX-ITI remote terminal

Read more
Make Schneider Electric
Manufacturer Schneider Electric
Category Transmission and Distribution>Switchgears
Model code FBX3NC0312A21WOC2O
Series FBX
Type Gas insulated switchboard
Max. Voltage 12 kV
Max. Current 630 A
Frequency 50 Hz
Standards IEC 62271-1
Protection IK07
Width 1130 mm
Depth 930 mm
Height 2100 mm
Weight 515 kg Kg
Additional info
  • SF6-insulated switchgear for secondary distribution network
  • SF6 switch-disconnector
  • Protection through fuse combination or vacuum circuit-breaker
  • Two versions : FBX-C (Compact), FBX-E (Extensible)
  • Compliant with IEC 62271-200
  • Rated Voltage: 12 / 17.5 / 24 kV
  • Bus-bar Rated Current: 630 A
  • Feeder Rated Current: 630 A
  • Rated Short Time Withstand Current : up to 21 kA 3s (up to 25 kA 1s for 12 kV)
  • Internal Arc Containment : up to 25 kA 1s
  • Dimensions W x H x D in mm: 2 switch-disconnectors + circuit-breaker or fuse protection functions:
  • 1000 x 1380 x 750
  • Option : can be remotely controlled and monitored through a RCX-ITI remote terminal