A generator is a machine that converts mechanical power to electrical power, either AC or DC. The mechanical power can be provided by several different sources; such as a diesel or gasoline engine, water wheel, windmill, or electric motor. 

An alternator is a specific type of generator that converts mechanical power to AC electrical power. We will be focusing on alternators in this paper.

Excitation methods

There are different options for excitation methods. First is a self-excited system. The output from the alternator provides the power for the Automatic Voltage Regulator (AVR) as well as the sensing voltage to the regulator. 

The auxiliary winding is a separate single-phase winding that is inserted into the main stator

The second form of excitation is the separately excited method using a permanent magnet generator (PMG). This configuration has a small PMG mounted on the non-drive end that supplies power for the AVR.  The main generator output still supplies the sensing voltage. Another form of excitation uses an Auxiliary Winding. The auxiliary winding is a separate single-phase winding that is inserted into the main stator in the same slots as the main output winding. 

How does it work?

In the case of the PMG method of excitation, the PMG rotor produces a high-frequency AC voltage in the PMG stator which the AVR uses to supply DC to the exciter fields. This generates three-phase ac power in the exciter rotor which is rectified and fed into the main rotating fields.

The main DC fields generate AC output from the main stator which provides feedback to the AVR. Using the PMG allows the AVR excitation to remain at full capacity when sudden loads are applied to the generator, giving better motor starting performance. 

Component Characteristics and Testing

If the user needs to rewind the exciter rotor it must have the same number of poles as the exciter fields

The number of exciter poles is normally more than the main generator poles. This provides a higher frequency that when rectified gives a cleaner DC. The exciter fields are DC fields and can be voltage-dropped just like a field in a DC motor.

If the user needs to rewind the exciter rotor it must have the same number of poles as the exciter fields.

Diode bridge

The diode bridge has a positive rectifier plate and a negative rectifier plate. There is usually a suppressor across the rectifier plates that protects the diodes as well as the main stator.

A multimeter will read between 0.4 and 0.7 volts on the diode scale with the positive lead on the anode and negative lead on the cathode. If the user swaps the leads it will read open. If it reads open in both directions or shorted in both directions then the diode needs to be replaced.

Multimeter measurements

If the output from the PMG is too low then either the PMG is weak or there is a fault

The best way to test the PMG is while it is in service on the generator. Find the tag on the AVR to find the sensing voltage required and the required PMG output.

With a multimeter measure these voltages to verify that they are within range. If the output from the PMG is too low then either the PMG is weak or there is a fault in the PMG stator.

Controlled DC supply

A variac with both a rectified DC output and AC output is a very useful tool in testing a generator. It can be used to voltage drop the main rotor and the exciter fields with the controlled AC supply.

The controlled DC supply can be used to bypass the AVR and separately excite the exciter field. While applying DC directly to the exciter field of an unloaded generator user can measure the required DC input voltage and current to generate full voltage. This can be useful in sourcing an aftermarket AVR.

DC voltmeter

Adjust the pot to dim and brighten the bulb, return the pot to the original output voltage

A resistive load, such as an incandescent light bulb, is required to test the AVR. Connect the light bulb to the F+/F- of the AVR.

Apply the required supply voltage and sensing voltage to the AVR. Use a DC voltmeter to measure the output across F+ and F. Adjust the pot to dim and brighten the bulb. Return the pot to the original output voltage. 

If the user Has to Rewind the Generator  

Component Characteristics and Testing Before burnout, identify the leads. If there are leads other than output power leads, they may be taps or auxiliary windings to provide voltage for the AVR.

If there are taps or auxiliary windings present it is best to burn out the stator without cutting the coil end. 

Auxiliary windings

The main winding acts as the primary of a transformer and the auxiliary winding acts as the secondary

There can be more than one auxiliary winding. Some manufacturers use a single-phase transformer auxiliary winding and a load-dependent booster winding. For the auxiliary windings, it is all about location, location, and location just like in real estate. Mark a slot as #1, the main lead #1 is a good reference.

Draw a diagram of the auxiliary windings about the marked slot. Insert the main windings and auxiliary windings in the same slots. The main winding acts as the primary of a transformer and the auxiliary winding acts as the secondary. If the coils are not placed back in the same orientation, they may have incorrect voltage supplied to the AVR. 

Original winding data

When there are taps, count the number of coils to the main lead and the non-output lead. A tap may be within a coil so count the number of turns to the tap.

It is best to maintain the original winding data. It is common for a manufacturer to use a 2/3 pitch to eliminate third harmonics in the output. Always verify that the number of poles in the main stator matches the number of poles in the main rotor.

Download PDF version Download PDF version

In case you missed it

Vestel Mobility's Latest Charging Range At London EV Show 2024
Vestel Mobility's Latest Charging Range At London EV Show 2024

Vestel Mobility is pleased to announce its participation in the upcoming London Electric Vehicle Show (London EV Show) 2024, the UK’s foremost trade expo and conference dedic...

HENSOLDT Bolsters PCB Capacity In Electronics Hub
HENSOLDT Bolsters PCB Capacity In Electronics Hub

The sensor solutions provider - HENSOLDT is further expanding its production capacities at the Ulm site. A second printed circuit board assembly line has already been put into oper...

MOVE ON Energy Chooses Delta For 650MW Solar Project
MOVE ON Energy Chooses Delta For 650MW Solar Project

Delta, a global pioneer in power management and a provider of IoT-based smart green solutions, announced it has provided approximately 3,500 Delta M125HV PV inverters to MOVE ON En...

vfd