Explosionproof, Dust-Ignitionproof, Waterproof. Precision machined flame path between box and cover. O-ring gasket insures watertight integrity 65,000 AIC. Highest interrupt rated enclosure in the industry Bolt on slotted mounting feet Stainless steel, captive Quad-Lead® cover bolts (disengage in 1-½ turns) External stainless steel breaker operating handle Ground lug package and installation instructions for termination of ground wire enclosed Four point control terminal block, NEMA 1B with wire markers Breaker operators can be locked in the ON or OFF position (combination starters only) Four plugged ¾” NPSM outlets drilled and tapped for control devices Plugged ½” outlets top and bottom for optional breather/drain Components are mounted on a galvanized steel removable pan Enclosures are designed to accept Cutler-Hammer B, or Square D motor starters/circuit breakers. For other manufacturers, contact your local representative
Make | Appleton |
---|---|
Manufacturer | Emerson Electric Co. |
Model code | AELLBB4W1CU5 |
Series | Appleton™ AELB Series Bolted Motor Starters and Contactors |
Power rating | 125 HP |
Rated Voltage | 480 V |
Nema type | Size 5 |
Construction | Bodies and covers: copperfree (4/10 of 1%) aluminum / Block hinges, cover bolts, handle, breaker and operator shafts: stainless steel / O-ring: neoprene |
Standard | UL Standards: UL 50, UL 1203 ; UL Classified: E84577 |
Weight | 227 Kg |
Additional info |
|